Applications

PowerGuard® cables are intended for use in wet or dry locations for distribution of single or three phase medium-voltage power. These cables may be installed in ducts or direct buried.

Description

Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength PowerGuard® TRXLPE insulation, thermosetting semiconducting insulation shield, coppermore

Unit of Measure
Items
URD Cable Copper and Aluminum

PowerGuard® 15kV 100% MV TR-XLPE Aluminum Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07

URD Cable Copper and Aluminum

PowerGuard® 15kV 100% MV TR-XLPE Aluminum Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07

URD Cable Copper and Aluminum

PowerGuard® 15kV 100% MV TR-XLPE Aluminum Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07

URD Cable Copper and Aluminum

PowerGuard® 15kV 100% MV TR-XLPE Aluminum Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07

URD Cable Copper and Aluminum

PowerGuard® 15kV 100% MV TR-XLPE Aluminum Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07
Conductor
Size
AWG/kcmil
N/A 2 N/A 1/0 N/A 1/0 N/A 1/0 N/A 1/0
No
of
Wires
N/A 7 N/A 19 N/A 19 N/A 19 N/A 19
Nominal
Diameter
(in)
N/A 0.283 N/A 0.362 N/A 0.362 N/A 0.362 N/A 0.362
Neutral
Size
AWG/kcmil
N/A 10 N/A 12 N/A 13 N/A 10 N/A 7
Neutral
No.
of
Wires
N/A 14 N/A 14 N/A 16 N/A 16 N/A 16
Neutral
Size
N/A Full N/A Full N/A 2/3 N/A 1/2 N/A 1/3
TRXLPE
Insulation
Nominal
Thickness
(mils)
N/A 175
TRXLPE
Insulation
Minimum
Diameter
(in)
N/A 0.649 N/A 0.728 N/A 0.728 N/A 0.728 N/A 0.728
TRXLPE
Insulation
Maximum
Diameter
(in)
N/A 0.729 N/A 0.808 N/A 0.808 N/A 0.808 N/A 0.808
Encap
XLPE
Jacket
Nominal
Thickness
(mils)
N/A 60
Encap
XLPE
Jacket
Nominal
Diameter
(in)
N/A 1.037 N/A 1.116 N/A 1.090 N/A 1.090 N/A 1.090
Neutral
lbs/MFT
N/A 129 N/A 154 N/A 105 N/A 81 N/A 57
Net
lbs/MFT
N/A 583 N/A 651 N/A 585 N/A 563 N/A 541