Quadruplex Conductor 600V Secondary Type URD Cable Aluminum Conductor
Quadruplex Conductor Type URD Cable - Aluminum Conductor
Applications
Directly buried or installed in ducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified is desired.
Standards
Secondary URD quadruplex conductor 600V cable meets or exceeds the following ASTM specifications.
To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
Directly buried or installed in ducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified is desired.
Standards
Secondary URD quadruplex conductor 600V cable meets or exceeds the following ASTM specifications.
- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
- B-786 19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation.
- B-901 Compressed round stranded Aluminum Conductors using single input wire construction.
- Secondary UD quadruplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
- "USE-2" per UL 854 available upon request
- Cable in Duct (CIC)
- Abrasion Resistant
To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
Unit of Measure
Items |
/Asset/QUADRUPLEX-URD.jpg Tulsa Quadruplex Conductor 600V Secondary Type URD Cable Aluminum Conductor |
/Asset/QUADRUPLEX-URD.jpg Dyke Quadruplex Conductor 600V Secondary Type URD Cable Aluminum Conductor |
/Asset/QUADRUPLEX-URD.jpg Wittenberg Quadruplex Conductor 600V Secondary Type URD Cable Aluminum Conductor |
/Asset/QUADRUPLEX-URD.jpg Notre Dame Quadruplex Conductor 600V Secondary Type URD Cable Aluminum Conductor |
/Asset/QUADRUPLEX-URD.jpg Purdue Quadruplex Conductor 600V Secondary Type URD Cable Aluminum Conductor |
|||||
Phase Conductor Size/AWG |
N/A 4 | N/A 2 | N/A 2 | N/A 1/0 | N/A 1/0 | |||||
Phase Conductor Stranding |
N/A 7 | N/A 7 | N/A 7 | N/A 19 | N/A 19 | |||||
Phase Conductor Insulation Thickness |
N/A 60 mls | N/A 60 mls | N/A 60 mls | N/A 80 mls | N/A 80 mls | |||||
Neutral Size AWG | N/A 4 | N/A 4 | N/A 2 | N/A 2 | N/A 1/0 | |||||
Neutral Stranding | N/A 7 | N/A 7 | N/A 7 | N/A 7 | N/A 19 | |||||
Neutral Insulation Thickness | N/A 60 mls | N/A 60 mls | N/A 60 mls | N/A 60 mls | N/A 80 mls | |||||
Single Phase Conductor |
N/A .345 Inches | N/A .403 Inches | N/A .403 Inches | N/A .522 Inches | N/A .522 Inches | |||||
Outside Diameter |
N/A .833 Inches | N/A .938 Inches | N/A .973 Inches | N/A 1.188 Inches | N/A 1.260 Inches | |||||
Weight (lb/1000 ft) |
N/A 258 Lbs | N/A 346 Lbs | N/A 375 Lbs | N/A 541 Lbs | N/A 596 Lbs | |||||
Ampacity Direct Burial |
N/A 119 Amps | N/A 153 Amps | N/A 153 Amps | N/A 198 Amps | N/A 198 Amps | |||||
Ampacity In Duct |
N/A 85 Amps | N/A 115 Amps | N/A 115 Amps | N/A 150 Amps | N/A 150 Amps | |||||
|