Applications
Covered Line Wire is used primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.

Construction
Conductors are aluminum alloy 1350-H19, 6201-181, or ACSR conductors, concentrically stranded and covered for weather proofing with polyethylene, high density polyethylene (HD) or crosslinked polyethylene (XLP).

Standards
  • ASTM B-230 - Aluminum 1350-H19 Wire for Electrical Purposes.
  • ASTM B-231 -
  • more
Unit of Measure
Items
AL Covered Line Wire

Covered Line Wire Alloy 6201 Aluminum Conductor

AL Covered Line Wire

Covered Line Wire Alloy 6201 Aluminum Conductor

AL Covered Line Wire

Covered Line Wire Alloy 6201 Aluminum Conductor

AL Covered Line Wire

Covered Line Wire Alloy 6201 Aluminum Conductor

AL Covered Line Wire

Covered Line Wire Alloy 6201 Aluminum Conductor
Size
(AWG or kcmil)
N/A 4 N/A 2 N/A 1/0 N/A 2/0 N/A 3/0
Strand N/A 7/w
Insulation
Thickness
(mils)
N/A 30 mls N/A 45 mls N/A 60 mls N/A 60 mls N/A 60 mls
Outside
Diameter
N/A .310 Inches N/A .406 Inches N/A .518 Inches N/A .567 Inches N/A .622 Inches
Rated
Breaking
Strength
N/A 1480 Lbs N/A 2520 Lbs N/A 4010 Lbs N/A 4850 Lbs N/A 6110 Lbs
Weight
Per
(lb/1000 ft)
XLP
N/A 62.1 Lbs N/A 96.1 Lbs N/A 166.1 Lbs N/A 203.3 Lbs N/A 249.4 Lbs
Weight
(lb/1000 ft)
Poly
N/A 60.1 Lbs N/A 93.3 Lbs N/A 160.0 Lbs N/A 196.4 Lbs N/A 241.4 Lbs
Ampacity
XLP
N/A 145 Amps N/A 190 Amps N/A 250 Amps N/A 290 Amps N/A 335 Amps