Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER
Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER
Applications
As flame-retardant three or four conductor power cables rated 600V, 90°C in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Type TC cable is also approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Construction
Class B stranded uncoated copper conductor, FR-XLPE flame-retardant cross-linked polyethylene insulation, surface print phase identification. Three or four insulated conductors twisted with a Class B stranded uncoated copper grounding conductor and suitable fillers, cable tape, helical copper tape shield, PVC jacket overall, surface printed
Standards
- Listed by UL as Type TC per Standard 1277 for Tray Cables.
- Individual conductors UL listed as Type XHHW-2.
- Individual conductors pass UL VW-1 flame test.
- Overall jacket UL listed as Sunlight Resistant and Oil Resistant II.
- Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hr test.
- Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
- Cables UL listed for Direct Burial.
- Cables UL listed for Open Wiring.
- Cables meet requirements of ICEA S-95-658/NEMA WC70.
- Color Code ICEA Method 4.
- Ampacity in accordance with the National Electrical Code for cables in uncovered cable tray without maintained spacing and for cables in raceway or directly buried; at the conductor temperature indicated, in wet or dry locations, 30°C ambient temperature.
- Grounding conductor per UL Standard 1277 for Type TC Tray Cable.
Items |
![]() 8-02XHPGTCS Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER |
![]() 8-03XHPGTCS Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER |
![]() 8-04XHPGTCS Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER |
![]() 6-02XHPGTCS Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER |
![]() 6-03XHPGTCS Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER |
|||||
Size AWG or MCM |
N/A 8 | N/A 8 | N/A 8 | N/A 6 | N/A 6 | |||||
No. of Conductors |
N/A 2 | N/A 3 | N/A 4 | N/A 2 | N/A 3 | |||||
No. of Strands |
N/A 7 | |||||||||
Nominal OD (inches) |
N/A 0.14 | N/A 0.14 | N/A 0.14 | N/A 0.18 | N/A 0.18 | |||||
Insulation (mils) |
N/A 45 | |||||||||
Overall Jacket (mils) |
N/A 60 | |||||||||
Ground Wire AWG |
N/A 10 | N/A 10 | N/A 10 | N/A 8 | N/A 8 | |||||
Approximate OD |
N/A 0.65 | N/A 0.7 | N/A 0.76 | N/A 0.73 | N/A 0.78 | |||||
Approximate Net Weight (lbs/MFT) |
N/A 307 | N/A 370 | N/A 450 | N/A 423 | N/A 510 | |||||
|