Applications
As flame-retardant multi-conductor control, signal or power cables rated 600V, 90°C in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class I remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.
Construction
Stranded uncoated copper conductors, 30 mils FR-XLPE flame-retardant cross-linked polyethylene insulation, color coded, conductors twisted with suitable fillers where necessary to make round, cable tape, helically applied copper tape shield, PVC jacket overall, surface printed.
Specifications
- Listed by UL as Type TC or TC-ER per Standard 1277 for Tray Cables.
- Cables UL listed for Direct Burial.
- Individual conductors pass UL VW-1 flame test.
- Individual conductors UL listed as Type XHHW-2.
- Overall jacket UL listed as Sunlight Resistant.
- Cables with grounding conductor UL listed for Open Wiring.
- Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hr test.
- Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
- Cables meet requirements of ICEA S-73-532, NEMA WC57 for Control Cables.
Notes
- Cables may be supplied with an insulated ground and marked “Open Wiring.”
- Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73- 532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.
Conductor
|
N/A 16 |
Number
|
N/A 3 |
O.A.
|
N/A 45 |
O.D.
|
N/A 0.37 |
Weight
|
N/A 84 |