Applications
As flame-retardant three or four conductor power cables rated 600V, 90°C in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Type TC cable is also approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Construction
Class B stranded uncoated copper conductor, FR-XLPE flame-retardant cross-linked polyethylene insulation, surface print phase identification. Three or four insulated conductors twisted with a Class B stranded uncoated copper grounding conductor and suitable fillers, cable tape, helical copper tape shield, PVC jacket overall, surface printed
Standards
- Listed by UL as Type TC per Standard 1277 for Tray Cables.
- Individual conductors UL listed as Type XHHW-2.
- Individual conductors pass UL VW-1 flame test.
- Overall jacket UL listed as Sunlight Resistant and Oil Resistant II.
- Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hr test.
- Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
- Cables UL listed for Direct Burial.
- Cables UL listed for Open Wiring.
- Cables meet requirements of ICEA S-95-658/NEMA WC70.
- Color Code ICEA Method 4.
- Ampacity in accordance with the National Electrical Code for cables in uncovered cable tray without maintained spacing and for cables in raceway or directly buried; at the conductor temperature indicated, in wet or dry locations, 30°C ambient temperature.
- Grounding conductor per UL Standard 1277 for Type TC Tray Cable.
Size
|
N/A 500 |
No.
|
N/A 4 |
No.
|
N/A 37 |
Nominal
|
N/A 0.74 |
Insulation
|
N/A 65 |
Overall
|
N/A 110 |
Ground
|
N/A 2 |
Approximate
|
N/A 2.38 |
Approximate
|
N/A 7745 |