APPLICATIONS
Used for overhead electrical transmission and distribution lines, grounding electrical systems, electrical test equipment and other infrastructure.

CONSTRUCTION
Conductors:
Concentric-lay stranded bare copper conductors available in soft, medium hard, or hard temper. Stranded tin coated copper conductors available in soft temper only.

STANDARDS
  • ASTM B1 - Hard-drawn copper wire
  • ASTM B2 - Medium hard-drawn copper wire
  • ASTM B3 - Soft or annealed copper wire
  • ASTM B8 - Concentric-lay stranded copper conductors: all tempers
  • ASTM B258 - Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  • Federal Specification QQ-W-343 - Wire, Electrical, Copper (Uninsulated)

NOTES
Dimensions and weights are nominal values, subject to standard manufacturing tolerances. Conductor ampacities are in accordance with the NEC, latest edition.



Updated 12/6/2021

Unit of Measure

Specifications

Item #
Soft

N/A 350-01BC3700

Item #
Medium

N/A 350-01BC3710

Item #
Hard

N/A 350-01BC3720

Size
(AWG
or
kcmil)

N/A 350

Strands
(#)

N/A 37

Overall
Diameter
(in)

N/A 0.681

Weight
(lb/1000 ft)

N/A 1081.0

Breaking
Strength
Soft
(lbf)

N/A 10580

Breaking
Strength
Medium
(lbf)

N/A 12450

Breaking
Strength
Hard
(lbf)

N/A 16060

Ampacity

N/A 650