1) Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.
2) Resistance is calculated using metal conductivity of 61.2% IACS for EC (1350) at 20ºC and 8% IACS for steel at 20ºC.
3) Ampacities are based on 75ºC conductor temperature, 25ºC ambient, 2 ft/s wind, full sun, an emissivity of 0.91 and a coefficient of solar absorption of 0.91, at sea level. Thermal resistivity of covering is 375ºC-cm/Watt.
UPDATED 06/12/2023
Items |
![]() Walnut Covered Line Wire ACSR Aluminum Conductor |
![]() Butternut Covered Line Wire ACSR Aluminum Conductor |
![]() Hickory Covered Line Wire ACSR Aluminum Conductor |
![]() Pignut Covered Line Wire ACSR Aluminum Conductor |
![]() Beech Covered Line Wire ACSR Aluminum Conductor |
|||||
Size AWG /KCMIL |
N/A 6 | N/A 4 | N/A 4 | N/A 2 | N/A 2 | |||||
Stranding | N/A 6/1 | |||||||||
Conductor Diameter (in) |
N/A 0.198 | N/A 0.250 | N/A 0.257 | N/A 0.316 | N/A 0.325 | |||||
Covering Thickness (in) |
N/A 0.030 | N/A 0.030 | N/A 0.030 | N/A 0.045 | N/A 0.045 | |||||
Overall Diameter (in) |
N/A 0.258 | N/A 0.310 | N/A 0.317 | N/A 0.406 | N/A 0.415 | |||||
AL Weight (lb/1000 ft) |
N/A 24.5 | N/A 38.9 | N/A 38.9 | N/A 61.9 | N/A 61.9 | |||||
STEEL Weight (lb/1000 ft) |
N/A 11.6 | N/A 18.4 | N/A 28.0 | N/A 29.3 | N/A 44.7 | |||||
NET Weight (lb/1000 ft) |
N/A 45.5 | N/A 68.8 | N/A 78.7 | N/A 113.5 | N/A 129.5 | |||||
Rated Strength |
N/A 1190 | N/A 1860 | N/A 2360 | N/A 2850 | N/A 3640 | |||||
DC Resistance @ 20 deg C (ohm/1000 ft) |
N/A 0.6410 | N/A 0.4030 | N/A 0.3990 | N/A 0.2540 | N/A 0.2510 | |||||
Ampacity (A) |
N/A 105 | N/A 140 | N/A 140 | N/A 185 | N/A 180 | |||||
|