Construction
Conductor: Class A or B compressed concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
Insulation: Extruded, Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649 - 100% insulation level.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.
Water-blocking agents: Applied over the insulation shield and around the neutral wires to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1 hour.
Outer jacket: An extruded-to-fill black non-conducting cross-linked polyethylene jacket, meeting the physical requirements the tables below, when tested by the methods specified in ANSI/ICEA S-94-649. The jacket shall be free-stripping and not interfere with contact between the neutral wires and the underlying extruded insulation shield. The jacket is sunlight resistant. The jacket shall contain a print legend marking, sequential length marking and three longitudinal extruded red stripes.
Designed for 40 years of service.
Physical Properties of Extruded-to-Fill XLPE Jacket
|
|
Unaged Tensile Strength, min. (PSI) | 1500 |
Aged* Tensile Strength, min. ret. (%) | 70 |
Unaged Elongated, min. (%) | 150 |
Aged* Elongated, min. ret. (%) | 70 |
Heat Distortion 1 hr at 131 ºC, max. (%) | 30 |
Insulation Temperature Rating | |
Normal | 105º C |
Emergency* | 140º C |
Short Circuit - Shield | 350º C |
Short Circuit - Conductor | 250º C |
Items |
![]() A1/0-01UD35GT101X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - PHYSICAL PROPERTIES (COMPRESSED) |
![]() A1/0-01UD35GT203X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - PHYSICAL PROPERTIES (COMPRESSED) |
![]() A1/0-01UD35GT102X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - PHYSICAL PROPERTIES (COMPRESSED) |
![]() A1/0-01UD35GT103X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - PHYSICAL PROPERTIES (COMPRESSED) |
![]() A2/0-01UD35GT101X PowerGuard® 35kV MV TR-XLPE AL Collection System Cable XLPE Jacket UL MV-105/AEIC CS8-07 - PHYSICAL PROPERTIES (COMPRESSED) |
|||||
Conductor AL Size AWG or kcmil |
N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 1/0 | N/A 2/0 | |||||
Neutral Size |
N/A Full | N/A 2/3 | N/A 1/2 | N/A 1/3 | N/A Full | |||||
Neutral # of Wires (Size of Wires) |
N/A 12 (14) | N/A 13 (16) | N/A 10 (16) | N/A 7 (16) | N/A 15 (14) | |||||
Conductor Nominal Diameter (in) |
N/A 0.3620 | N/A 0.3620 | N/A 0.3620 | N/A 0.3620 | N/A 0.4060 | |||||
Insulation Minimum Diameter (in) |
N/A 1.0450 | N/A 1.0450 | N/A 1.0450 | N/A 1.0450 | N/A 1.0900 | |||||
Insulation Maximum Diameter (in) |
N/A 1.1450 | N/A 1.1450 | N/A 1.1450 | N/A 1.1450 | N/A 1.1900 | |||||
Jacket Nominal Diameter (in) |
N/A 1.4090 | N/A 1.3820 | N/A 1.3820 | N/A 1.3820 | N/A 1.4530 | |||||
AL Weight lb/MFT |
N/A 99 | N/A 99 | N/A 99 | N/A 99 | N/A 125 | |||||
CU Weight lb/MFT |
N/A 153 | N/A 104 | N/A 80 | N/A 56 | N/A 192 | |||||
Net Weight lb/MFT |
N/A 946 | N/A 869 | N/A 850 | N/A 831 | N/A 1038 | |||||
|