NOTES
Dimensions and weights are nominal values, subject to standard manufacturing tolerances. The ampacity rating and the DC and AC resistance of the Copper Clad steel wire conductor is not equivalent to that of a copper conductor.
To select the correct equivalent please see — Proper Product Sizing: Diameter Comparison for Copper Equivalent Fusing Current for Grounding Applications.
Updated 12/6/2021
Items |
![]() 1#6 Copper Clad Steel Wire |
![]() 1#4 Copper Clad Steel Wire |
![]() 1#2 Copper Clad Steel Wire |
![]() 7#9 Copper Clad Steel Wire |
![]() 7#8 Copper Clad Steel Wire |
|||||
Cross- Sectional Area (in²) |
N/A 0.02061 | N/A 0.03278 | N/A 0.05212 | N/A 0.07195 | N/A 0.09078 | |||||
Cross- Sectional Area (mm²) |
N/A 13.3 | N/A 21.15 | N/A 33.62 | N/A 46.42 | N/A 58.57 | |||||
Strands (#) |
N/A Solid | N/A Solid | N/A Solid | N/A 7 | N/A 7 | |||||
Diameter of Wires (in) |
N/A 0.1620 | N/A 0.2043 | N/A 0.2576 | N/A 0.1144 | N/A 0.1285 | |||||
Diameter Overall (in) |
N/A 0.162 | N/A 0.204 | N/A 0.258 | N/A 0.343 | N/A 0.385 | |||||
WEIGHT (lb/ft) |
N/A 0.074 | N/A 0.117 | N/A 0.186 | N/A 0.259 | N/A 0.327 | |||||
Minimum Breaking Strength (lb) |
N/A 720 | N/A 1145 | N/A 1821 | N/A 2650 | N/A 3350 | |||||
Maximum Resistance DC @ 20 °C Ohm/1000ft |
N/A 1 | N/A 0.629 | N/A 0.396 | N/A 0.2916 | N/A 0.2311 | |||||
|