Applications
These cables are suitable for use installed in cable trays, direct burial, and raceways or when supported by a messenger wire. Voltage ratings not to exceeding 600 volts and conductor temperatures not to exceed 90°C dry or 90°C wet. Cables pass the UL 1277 Vertical Tray Flame Test and the IEEE 1202/FT4 flame test.
Construction
This specification covers the construction requirements of multi-conductor power cables in accordance with UL, Inc. Standard 1277, (UL) Listed as Type TC-ER. (Exposed Run)
The construction consists of stranded, bare copper conductors with cross-lined polyethylene (XLPE) insulation. The conductors are cabled together and have a sunlight resistant, Polyvinyl Chloride (PVC) jacket. - Sequential Marking
Compliances
- 600 Volts, 90°C dry, 90° wet
- XHHW-2 Conductors (XLPE)
- PVC Jacket
- FT4 / IEEE 1202, Sunlight Resistant, Direct Burial
- UL Standard 1277, (UL) Listed as Type TC-ER. (Exposed Run)
Component
Number
|
# of
Cond.
|
Size
AWG/MCM
|
# of
Strands
|
Nominal
Cond.
|
Insulation
Wall
Nominal
|
Nominal
Jacket
Wall
|
Nominal
O.D.
|
Net Weight
|
|
|
|
|
DCR M
|
Inches
|
MM
|
Inches
|
MM
|
Inches
|
MM
|
LB./kft.
|
kg/km
|
Component 1
|
3
|
3
|
19 Str
|
0.21
|
0.051
|
1.30
|
0.082
|
2.08
|
1.024
|
26.01
|
2024
|
3012
|
Component 2
|
1
|
6
|
19 Str
|
0.42
|
0.037
|
0.94
|
|
|
|
|
|
|
Component 3
|
6
|
18
|
16/30
|
6.40
|
0.021
|
0.53
|
|
|
|
|
|
|