• ASTM B230 – Aluminum 1350–H19 Wire for Electrical Purposes
• ASTM B231 – Concentric-Lay-Stranded Aluminum 1350 Conductors
• ASTM B232 – Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR)
• ASTM B498 – Zinc-Coated (Galvanized) Steel Core Wire for Use in Overhead Electrical Conductors
• CSA C60888 – Zinc-coated steel wires for stranded conductors
• CSA C60889 – Hard-drawn aluminum wire for overhead line conductors
• CSA C61089 – Round wire concentric lay overhead electrical stranded conductors
Options
NOTES
1) Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.
2) Resistance is calculated using metal conductivity of 61.2% IACS for EC (1350) at 20ºC and 8% IACS for steel at 20ºC.
3) Ampacities are based on 75ºC conductor temperature, 25ºC ambient, 2 ft/s wind, full sun, an emissivity of 0.5 and a coefficient of solar absorption of 0.5, at sea level.
UPDATED 07/14/2023
Code Name |
N/A Starling |
Meets
|
N/A Yes |
Size
|
N/A 715.5 |
Stranding
|
N/A 26/7 |
Wire
|
N/A 0.1659 |
Wire
|
N/A 0.1290 |
Diameter
|
N/A 0.3870 |
Diameter
|
N/A 1.051 |
Weight
|
N/A 674.0 |
Weight
|
N/A 309.7 |
Weight
|
N/A 983.7 |
Rated
|
N/A 28400 |
Resistance
|
N/A 0.024 |
Allowable
|
N/A 849 |