Print Back

Powerguard® Medium Voltage Cable in Duct

Duct Materials

The duct shall be extruded from either medium density polyethylene type II, class C, category 5, or high density polyethylene type III, class C, category 5 as outlined in ASTM D1248.

Duct Dimensions
The following duct dimensions are recommended, however, AWG will provide duct to customer's required dimensions when specified.

Contact us for compatible cable constructions.


The cable shown in the illustration is PowerGuard® 35kV MV Aluminum TR-XLPE Collection System Cable LLDPE Jacket UL MV-90/AEIC CS8-07



UPDATED 02/14/2024

Unit of Measure

Specifications

Conduit
Size

N/A 2 Inches

Conduit
Outer
Diameter

N/A 2.38 Inches

Minimum
Wall
Thickness

N/A 145 mls

Bending
Radius

N/A 26 Inches

Max.
Cable
Diameter

N/A 1.5 Inches

Typical
Unjacketed
Cond. Size

N/A 4/0 through 500

Tensile Strength Min. - Medium

N/A 2400 psi

Tensile Strength Min. - High

N/A 3200 psi

Elongation

N/A 400 %

Melt
Index
Max.

N/A .4

Thermal Stress Crack Resistance-no cracking, hrs, min. - Medium

N/A 96 hrs

Thermal Stress Crack Resistance-no cracking, hrs, min. - High

N/A 168 hrs

Environmental Stress Crack Resistance-hrs to 20% Failure min. 48 - Medium

N/A 48 min.

Environmental Stress Crack Resistance-hrs to 20% Failure min. 48 - High

N/A 48 min.

Brittleness
Temp.
ºC max.
Medium

N/A -45 ºC

Brittleness
Temp.
ºC max.
High

N/A -75 ºC

Note

N/A

  • Schedule 40 duct also available