Application
For runway, taxiway and approach in underground series airport lighting circuits. At 5,000 V rated voltage and maximum conductor temperatures of 90 ºC for continuous normal operation and 250 ºC for short circuit.
Suitable for use in wet or dry conditions in metallic and non-metallic conduits, ducts, aerial and direct earth burial installations.

Construction
A bare copper seven wires stranded circular conductor covered with a separator tape has an extruded tracking resistant XLPE (crosslinked polyethylene) insulation, non-jacketed.

Also available with conductor shield, insulation shield and / or PVC or PE jacket, upon request.

Standard supply lengths are 5000 ft / reel. Other reel lengths are available upon request.

Flexible stranding of 19 strands available.

Standards
Conforms to:
  • FAA Advisory Circular (AC)150/5345-7E, Specification for L-824 Type C
  • L824 Type B also available.
  • NEMA WC71 / ICEA S-96-659-1999 for non-shielded cables.
Certification
  • ETL Certified.
  • FAA Listed as an Approved Supplier
1 - 3 of 3 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

No. of
Strands
in
Conductor

Nominal
Diameter
of
Conductor
(inches)

DC
Resistance
of
Conductor
at 25 ºC
per MFT

Separator
Tape
Thickness
(mils)

Nominal
Thickness
of
Insulation
(Inches)

Nominal
Diameter
(Inches)

Ampacity
Underground
Duct

N/A 8 N/A 7 N/A 0.143 N/A 0.652 N/A 0.5 N/A 110 N/A 0.364 N/A 64
N/A 6 N/A 7 N/A 0.180 N/A 0.411 N/A 0.5 N/A 110 N/A 0.401 N/A 85
N/A 4 N/A 7 N/A 0.226 N/A 0.258 N/A 0.5 N/A 110 N/A 0.447 N/A 110
1 - 3 of 3 | Results Per Page | View | Unit of Measure
1