14 AWG FR-XLPE Insulated Conductors CU Shield, CPE Jacket, 600V
Control Cable FR-XLPE Insulated Conductors, Copper Tape Shield, CPE Jacket, 600V
"Applications
Control or signal cable for important circuits in industrial plants and station control cable for electric utilities where flame resistance is essential. Suitable for the operation and interconnection of protective devices; rated circuit voltage 600 volts; recommended for operation at 90 ºC maximum continuous conductor temperature in wet or dry locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, and are suitable for direct burial. Utility grade meets or exceeds all UL requirements.
Construction
Stranded coated copper conductors. The insulation shall be either fire retardant ethylene propylene rubber (EPR) or fire retardant cross-linked Polyethylene (FR-XLPE). ICEA Appendix E Method 1 color-coded, conductors twisted with suitable fillers, helically applied copper tape shield, CPE jacket overall, surface printed.
Standards
Control or signal cable for important circuits in industrial plants and station control cable for electric utilities where flame resistance is essential. Suitable for the operation and interconnection of protective devices; rated circuit voltage 600 volts; recommended for operation at 90 ºC maximum continuous conductor temperature in wet or dry locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, and are suitable for direct burial. Utility grade meets or exceeds all UL requirements.
Construction
Stranded coated copper conductors. The insulation shall be either fire retardant ethylene propylene rubber (EPR) or fire retardant cross-linked Polyethylene (FR-XLPE). ICEA Appendix E Method 1 color-coded, conductors twisted with suitable fillers, helically applied copper tape shield, CPE jacket overall, surface printed.
Standards
- TC Type Tray Cable per Article 340 of the NEC.
- Individual conductors pass UL Standard 44 and the VW-1 vertical flame test.
- Individual conductors approved as Type XHHW.
- Cables Pass IEEE-383 ribbon burner flame test.
- Overall jacket approved as Sunlight Resistant.
- Cables meet requirements of ICEA Pub. No. S-73-532/NEMA WC74
- Cables may be supplied with an insulated ground and marked "Open Wiring."
- Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73-532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.
- Bare or Tinned Copper
- Flexible stranded conductors
- Color coding: ICEA Method 1, Table E1
- EPR Insulation
- PVC, CSPE, LSOH jackets
- Insulated ground wires or bare ground wires
- Overall copper tape shield
- Overall copper braid shield
- Overall longitudinal corrugated copper shield
- Overall mylar tape shield with drain wire
- 1000 volt rated construction
Item # |
Number
|
Number
|
Conductor
|
Overall
|
Overall
|
Weight
|
---|---|---|---|---|---|---|
14-402SH 14-402SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 2 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 45 |
Overall Diameter Inches (mm) N/A 0.40 |
Weight Per (lb/1000 ft) XLP N/A 120 Lbs |
14-403SH 14-403SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 3 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 45 |
Overall Diameter Inches (mm) N/A 0.42 |
Weight Per (lb/1000 ft) XLP N/A 145 Lbs |
14-404SH 14-404SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 4 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 45 |
Overall Diameter Inches (mm) N/A 0.45 |
Weight Per (lb/1000 ft) XLP N/A 180 Lbs |
14-405SH 14-405SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 5 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 45 |
Overall Diameter Inches (mm) N/A 0.49 |
Weight Per (lb/1000 ft) XLP N/A 230 Lbs |
14-406SH 14-406SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 6 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 60 |
Overall Diameter Inches (mm) N/A 0.53 |
Weight Per (lb/1000 ft) XLP N/A 275 Lbs |
14-407SH 14-407SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 7 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 60 |
Overall Diameter Inches (mm) N/A 0.60 |
Weight Per (lb/1000 ft) XLP N/A 275 Lbs |
14-408SH 14-408SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 8 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 60 |
Overall Diameter Inches (mm) N/A 0.70 |
Weight Per (lb/1000 ft) XLP N/A 305 Lbs |
14-409SH 14-409SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 9 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 60 |
Overall Diameter Inches (mm) N/A |
Weight Per (lb/1000 ft) XLP N/A |
14-412SH 14-412SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 12 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 60 |
Overall Diameter Inches (mm) N/A 0.89 |
Weight Per (lb/1000 ft) XLP N/A 435 Lbs |
14-414SH 14-414SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 14 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 0.96 |
Weight Per (lb/1000 ft) XLP N/A 530 Lbs |
14-415SH 14-415SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 15 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.04 |
Weight Per (lb/1000 ft) XLP N/A 565 Lbs |
14-416SH 14-416SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 16 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.05 |
Weight Per (lb/1000 ft) XLP N/A 575 Lbs |
14-418SH 14-418SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 18 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.07 |
Weight Per (lb/1000 ft) XLP N/A 665 Lbs |
14-419SH 14-419SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 19 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.09 |
Weight Per (lb/1000 ft) XLP N/A 665 Lbs |
14-420SH 14-420SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 20 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.10 |
Weight Per (lb/1000 ft) XLP N/A 720 Lbs |
14-425SH 14-425SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 25 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.22 |
Weight Per (lb/1000 ft) XLP N/A 905 Lbs |
14-427SH 14-427SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 27 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.25 |
Weight Per (lb/1000 ft) XLP N/A 905 Lbs |
14-429SH 14-429SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 29 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.26 |
Weight Per (lb/1000 ft) XLP N/A 960 Lbs |
14-431SH 14-431SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 31 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.31 |
Weight Per (lb/1000 ft) XLP N/A 1090 Lbs |
14-432SH 14-432SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 32 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.34 |
Weight Per (lb/1000 ft) XLP N/A 1090 Lbs |
14-437SH 14-437SH/Asset/xlpe-copper-shield.jpg |
Number of Conductors N/A 37 |
Number of Strands N/A 7 |
Conductor Size AWG N/A 14 |
Overall Mils N/A 80 |
Overall Diameter Inches (mm) N/A 1.39 |
Weight Per (lb/1000 ft) XLP N/A 1165 Lbs |