Applications
As flame-retardant multi-conductor control, signal or power cables rated 600V, 90°C in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class I remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.
Construction
Stranded uncoated copper conductors, 30 mils FR-XLPE flame-retardant cross-linked polyethylene insulation, color coded, conductors twisted with suitable fillers where necessary to make round, cable tape, helically applied copper tape shield, PVC jacket overall, surface printed.
Specifications
- Listed by UL as Type TC or TC-ER per Standard 1277 for Tray Cables.
- Cables UL listed for Direct Burial.
- Individual conductors pass UL VW-1 flame test.
- Individual conductors UL listed as Type XHHW-2.
- Overall jacket UL listed as Sunlight Resistant.
- Cables with grounding conductor UL listed for Open Wiring.
- Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hr test.
- Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
- Cables meet requirements of ICEA S-73-532, NEMA WC57 for Control Cables.
Notes
- Cables may be supplied with an insulated ground and marked “Open Wiring.”
- Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73- 532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.
Item # |
Conductor
|
Number
|
O.A.
|
O.D.
|
Weight
|
---|---|---|---|---|---|
10-02XHPTCS 10-02XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 2 |
O.A. (mils) N/A 45 |
O.D. (inch) N/A 0.47 |
Weight (lb/1000 ft) N/A 135 |
10-03XHPTCS 10-03XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 3 |
O.A. (mils) N/A 45 |
O.D. (inch) N/A 0.5 |
Weight (lb/1000 ft) N/A 178 |
10-04XHPTCS 10-04XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 4 |
O.A. (mils) N/A 60 |
O.D. (inch) N/A 0.53 |
Weight (lb/1000 ft) N/A 241 |
10-05XHPTCS 10-05XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 5 |
O.A. (mils) N/A 60 |
O.D. (inch) N/A 0.63 |
Weight (lb/1000 ft) N/A 294 |
10-07XHPTCS 10-07XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 7 |
O.A. (mils) N/A 60 |
O.D. (inch) N/A 0.68 |
Weight (lb/1000 ft) N/A 378 |
10-09XHPTCS 10-09XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 9 |
O.A. (mils) N/A 60 |
O.D. (inch) N/A 0.8 |
Weight (lb/1000 ft) N/A 487 |
10-12XHPTCS 10-12XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 12 |
O.A. (mils) N/A 80 |
O.D. (inch) N/A 0.91 |
Weight (lb/1000 ft) N/A 653 |
10-15XHPTCS 10-15XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 15 |
O.A. (mils) N/A 80 |
O.D. (inch) N/A 1.05 |
Weight (lb/1000 ft) N/A 836 |
10-19XHPTCS 10-19XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 19 |
O.A. (mils) N/A 80 |
O.D. (inch) N/A 1.1 |
Weight (lb/1000 ft) N/A 1001 |
10-25XHPTCS 10-25XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 25 |
O.A. (mils) N/A 80 |
O.D. (inch) N/A 1.28 |
Weight (lb/1000 ft) N/A 1333 |
10-31XHPTCS 10-31XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 31 |
O.A. (mils) N/A 80 |
O.D. (inch) N/A 1.38 |
Weight (lb/1000 ft) N/A 1529 |
10-37XHPTCS 10-37XHPTCS/Asset/Control-Cable-UL-Type-TC-or-TC-ER.jpg |
Conductor Size AWG N/A 10 |
Number of Conductors N/A 37 |
O.A. (mils) N/A 80 |
O.D. (inch) N/A 1.46 |
Weight (lb/1000 ft) N/A 1905 |